Voltage Drop Cable Chart
Cable Size Recommendation for Pumps
A voltage drop chart for cables is used to determine how much voltage is lost due to resistance as electricity travels through a wire. This is particularly important for long cable runs to ensure that the voltage at the load end is sufficient for the equipment to function properly.
| Motor (kW) 240v | Maximum Length of Cables in metres | |||||
| 1.5mm | 2.5mm | 4mm | 6mm | 10mm | 16mm | |
| 0.37 | 80 | 130 | 230 | 350 | 580 | 1000 |
| 0.55 | 55 | 90 | 140 | 200 | 350 | 700 |
| 0.75 | 40 | 65 | 105 | 160 | 300 | 500 |
| 1.1 | 30 | 50 | 75 | 115 | 190 | 400 |
| 1.5 | 25 | 35 | 60 | 90 | 145 | 230 |
| 2.2 | – | 30 | 50 | 70 | 120 | 185 |
| Motor (kW) 415v | Maximum Length of Cables in metres | |||||
| 1.5mm | 2.5mm | 4mm | 6mm | 10mm | 16mm | |
| 0.37 | 400 | 500 | 600 | 850 | 1000 | 1300 |
| 0.55 | 315 | 430 | 600 | 700 | 900 | 1200 |
| 0.75 | 240 | 350 | 500 | 650 | 750 | 1000 |
| 1.1 | 180 | 285 | 350 | 450 | 600 | 900 |
| 1.5 | 135 | 225 | 360 | 470 | 600 | 900 |
| 2.2 | 100 | 165 | 255 | 390 | 450 | 700 |
| 3 | 65 | 110 | 180 | 255 | 420 | 560 |
| 4 | 50 | 85 | 135 | 195 | 330 | 500 |
| 5.5 | 40 | 70 | 110 | 165 | 270 | 390 |
| 7.5 | 30 | 55 | 90 | 130 | 220 | 495 |
| 9.2 | – | 52 | 84 | 126 | 210 | 337 |
| 11 | – | – | 70 | 106 | 176 | 282 |
| 13 | – | – | 60 | 90 | 149 | 239 |
| 15 | – | – | – | 78 | 130 | 208 |
| 18.5 | – | – | – | – | 105 | 170 |
| 22 | – | – | – | – | 89 | 139 |
| Max volt drop allowed is 2.5% which is 6v at 230v e.g. 1.1kW single phase motor on 150m of cable will need 10mm cable, the maximum run on 10mm is 190m. | ||||||