Cable Size Recommendation for Pumps

A voltage drop chart for cables is used to determine how much voltage is lost due to resistance as electricity travels through a wire. This is particularly important for long cable runs to ensure that the voltage at the load end is sufficient for the equipment to function properly.

Motor (kW) 240v Maximum Length of Cables in metres
1.5mm 2.5mm 4mm 6mm 10mm 16mm
0.37 80 130 230 350 580 1000
0.55 55 90 140 200 350 700
0.75 40 65 105 160 300 500
1.1 30 50 75 115 190 400
1.5 25 35 60 90 145 230
2.2 30 50 70 120 185

 

Motor (kW) 415v Maximum Length of Cables in metres
1.5mm 2.5mm 4mm 6mm 10mm 16mm
0.37 400 500 600 850 1000 1300
0.55 315 430 600 700 900 1200
0.75 240 350 500 650 750 1000
1.1 180 285 350 450 600 900
1.5 135 225 360 470 600 900
2.2 100 165 255 390 450 700
3 65 110 180 255 420 560
4 50 85 135 195 330 500
5.5 40 70 110 165 270 390
7.5 30 55 90 130 220 495
9.2 52 84 126 210 337
11 70 106 176 282
13 60 90 149 239
15 78 130 208
18.5 105 170
22 89 139
Max volt drop allowed is 2.5% which is 6v at 230v e.g. 1.1kW single phase motor on 150m of cable will need 10mm cable, the maximum run on 10mm is 190m.